Products
Your current location:Home > Products
Name:DRY TYPE HIGH VOLTAGE WALL BUSHINGS   Views:24029 Times
产品特点 Product features
无瓷、无气、不充油
防火、防爆
免维护
体积小、重量轻
能够在酷热(50℃)及严寒(-50℃)环境下正常运行
Non-porcelain,non-gas,unfilled oil
Fire proof,explosion proof
Maintenance-free
Smaller volume,lighter weight
Ambient air temperature form -50 ℃ to 50℃
■ 技术参数 Technical parameters
最高电压:40.5~252(245)kV
额定电流:100~5000A
额定频率:50Hz、60Hz
Highest voltage:40.5~252(245)kV
Rated current:100~5000A
Rated frequency:50Hz、60Hz
■ 环境条件 Environment condition
安装方式:户内-户外、户外-户内或户外-户外,水平安装或垂直安装。
环境温度:-50~50℃
海拔高度:不超过1000m(超过1000m时另议)
环境污秽等级:Ⅱ、Ⅲ、Ⅳ级
Installation way:indoor-indoor,outdoor-indoor or outdoor-ouitdoor,level installation or vertical installation.
Ambient air temperature:-50~50℃
Height:1000m(confering with consumer if above 1000m)
Pollution class: Ⅱ、Ⅲ、Ⅳ
■ 主要性能 Main performance
      产品性能满足GB/T4109《交流电压高于1000V的绝缘套管》及IEC60137《Insulated bushing for alternating voltages above 1000V》的要求。
The main performance of then product can satisfy the requests of GB/T4109 《Insulated bushing for alternating voltages above 1000V》and IEC 60137《Insulated bushing for alternating voltages above 1000V》.
(1)额定绝缘水平及局部放电水平 Rated insulation level and partial discharge level
最高电压
Highest voltage
Um(kV)
额定绝缘水平
Rated insulation level
局部放电水平
Partial discharge level
工频耐受电压
Power frequency withstand voltage
(kV)
雷电冲击耐受电压
Lightning impulse
withstand voltage
(kV)
局部放电测量电压
Partial discharge
test voltage
(kV)
局部放电量
Partial discharge
(pC)
      40.5 95 200 40.5/25 10/5
      52 95 250 52/32 10/5
      72.5 160 350 72.5/44 10/5
      126(123) 230 550 126/77 10/5
      145 275 650 145/188 10/5
      170 325 750 170/103 10/5
      252(245) 460 1050 252/153 10/5
(2)介质损耗因数 Dielectric loss factor
在10kV及1.05Um/√3电压下测量,介质损耗因数不大于0.005(测试温度为10~40℃ )。
Dielectric loss factor is not greater than 0.005 under 10kV and 1.05Um/√3kV(ambient air temperature 10~40℃).
(3)温升限值 Temperature rising limit
绕组最高温升不大于75K。
The highest temperature rising of winding is not greater than 75K.
(4)额定短时热电流(Ith)为额定电流的25倍,持续时间为1s。
Rated short-time thermal current is twenty-five times rated current when time keeps up 1 second.
(5)套管的弯曲耐受负荷 Bendingwith撒谈得load(N)
最高电压
Highest voltage
Um (kV)
额定电流 Rated current (A)
≤800 1000~1600 2000~2500 ≥3150
          40.5 1000 1250 2000 3150
          52 1000 1250 2000 3150
          72.5 1000 1250 2000 4000
          126(123) 1250 1600 2500 4000
          145 1250 1600 2500 4000
          170 1250 1600 2500 4000
          252(245) 1250 1600 2500 4000
■ 验收及维护 Acceptance and maintenance
        每只干式高于穿墙套管出厂前进行了工频耐压、局部放电测量、介质损耗因数测量及末屏耐压试验。到现场后,可以按BG50150《电气装置安装工程 电气设备交接试验标准》进行。干式高压穿墙套管基本不需要维护,每2~3年测量一次电容量及介质损耗因数即可。
Every dry type high voltage wall bushing has passed the tests including poewr frequency withstand voltage,partial discharge,dielectric loss factor,terminal withstand voltage before leaving the factory. We follow up GB50150 《Standard for hand-over test of electric equipment electric equipment installation engineering》when the products are handed over. In generally,the products need no maintenance basically.It is enough to check the primary winding capacity and dielectic loss factor every 2~3 years.
■ 运输及安装 Transportation and installation
运输时用防震材料包装,防止剧烈震动。
吊装时应防止硅橡胶伞裙受损。
出厂文件包括:产品合格证、试验报告和产品说明书,均放入包装箱内,与产品一起运输。
安装好后应将干式高压穿墙套管的末屏引线可靠接地。
The products should be packed by shockproof material when they are transported.
Pay attention to the silicon rubber umbrelas when the products are suspended.
Documents:certificate,test report,product manual.They should be put into packing box with the products.
Please earth reliably the terminal of the products after installing.
■ 订货须知 Notice for order
订货时至少需提出下述参数:
电气参数:最高电压、额定电流、额定短时热电流、户内及户外的外绝缘爬虫距离。
环境参数:环境温度、海拔高度、污秽等级、安装方式。
如需附设贯穿式电流互感器,还应按电流互感器订货须知提出相关参数,并明确电流互感器为贯穿式还是一体化。
如有特殊要求,可按用户需要进行设计。
You should specify the following parameters at least when ordering:
Electric parameters:Highest voltage,rated current,rated short-time thermal current,creapage distance.
Environment condition:ambient air temperature,height,pollution class,installation way.
You should offer correct parameters according to the requests of current transformer if you want to append wall bushing type current transformer,at then same time you shuould illuminate discerption type or integrated type.
We can offer the special products too.
【Back】
Copyright © 2011 ALL Rights Reserved  Liaoning Boji Electric Technology Co.,Ltd
Address:No.43, Lantang Road, Shoushan Industrial Park, Liaoyang County, Liaoyang City, Liaoning Province, China
Zip Code:111220   Tel:(86)-419-2639287   Fax:(86)-419-2639287   E-mail:jiaohong0103@163.com
Liao ICP Record No.11012854          Technical Support:STWH  Media Support:LYHR.CN